SINEAX HEAD MOUNT
TEMPERATURE TRANSMITTERS |
|
|
|
SINEAX VK 616 HEAD
MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX VK 616 Head
Mount Temperature Transmitter
|
|
|
SINEAX VK 616 is
a two-wire head-mounted temperature transmitter. It is designed for measuring
temperature in combination with thermocouples or resistance
thermometers.
Thermocouple nonlinearities are automatically compensated.
The output signal is a current in the range 4…20 mA. The input
variable and measuring range are programmed with the aid of a PC and
the corresponding software.
The sensor circuit is monitored for open
and short-circuits and the output responds in a defined manner if
one is detected.
The power supply of 12…30 V DC is connected together with the
signal by the two leads connected to the measurement output (loop
powered).
|
|
INPUT: Thermocouple,
RTD
|
OUTPUT: 4 to 20 mA
|
|
|
|
-
PC
Programmable
-
RTD and TC inputs
-
Two, three and four wire connection
-
Programmable Sensor Fault Response
-
Isolated and Non-Isolated Versions
-
12-30 VDC Loop-Powered
|
|
|
|
|
|
|
Temperatures with
resistance thermometers for two-, three- or four-wire
connection
Pt 100, IEC 60 751
Ni 100, DIN 43 760
|
Temperatures with
thermocouples
Type B, E, J, K, N,
R, S, T acc. to IEC 60 584-1
Type L and U, DIN 43 710
Type W5 Re/W26 Re,
Type W3 Re/W25 Re acc. to ASTM E 988-90 |
|
|
|
|
SINEAX
VK 626 HART HEAD MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX
VK 626 Hart Head Mount Temperature Transmitter
|
|
|
SINEAX VK 626 is
a two-wire head-mounted programmable temperature transmitter. It is designed for
measuring temperature in combination with thermocouples or
resistance thermometers.
Thermocouple non-linearities are automatically compensated. The
output signal is a current in the range 4…20 mA. Measured variable
and measuring range are programmed using a PC with a suitable
interface and running the programming software. The sensor circuit
is monitored for open and short-circuits and the output responds in
a defined manner if one is detected.
The power supply of (12…30 V DC) is connected together with the
signal by the two leads connected to the measurement output (loop
powered).
|
|
INPUT: Thermocouple,
RTD
|
OUTPUT: 4 to 20 mA
|
|
|
|
|
|
|
|
|
|
|
|
Temperatures with resistance
thermometers for two-, three- or four-wire connection
Pt 100, IEC 60 751
Ni 100, DIN 43 760
|
Temperatures with
thermocouples
Type B, E, J, K, N, R, S, T
acc. to IEC 60 584-1
Type L and U, DIN 43 710
Type W5 Re/W26 Re,
Type W3 Re/W25 Re acc. to ASTM E 988-90 |
|
|
|
|
SINEAX
VK 636 PROFIBUS-PA HEAD MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX
VK 636 Profibus-Pa Head Mount Temperature Transmitter
|
|
|
The SINEAX VK 636 is
a head-mounted temperature transducer for use in automation systems
with PROFIBUS.
It converts the measured value, i.e. the signal from a thermocouple
or a resistance thermometer to the PROFIBUS-PA format.
PROFIBUS-PA (Process Automation) is an open field bus
standard according to EN 50 170 and IEC 61 158-2 that requirements
of the process industries. Both the communication and power supply
are via the bus conductors. The measured variables, ranges and other
parameters can be configured and set on a PC (Master Class 2)
running the respective configuration software.
|
|
INPUT: Thermocouple,
RTD
|
OUTPUT: PROFIBUS-PA
|
|
|
|
|
|
|
|
|
|
|
|
Temperatures with resistance
thermometers for two-, three- or four-wire connection
Pt 100, IEC 60 751
Ni 100, DIN 43 760
|
Temperatures with
thermocouples
Type B, E, J, K, N, R, S, T
acc. to IEC 60 584-1
Type L and U, DIN 43 710
Type W5 Re/W26 Re,
Type W3 Re/W25 Re acc. to ASTM E 988-90 |
|
|
|
|
SINEAX PT 602 DIN MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX PT 602 DIN Mount Temperature Transmitter
|
|
|
SINEAX PT 602 is a DIN
Mount configurable temperature transducer for PT100, 1 or 2-channel.
Measuring transducer for the conversion of the resistance value from a
Pt 100 sensor into a linear temperature output signal. Depending upon
utilized variant, 2, 3 or 4-wire connection can be used for the Pt 100
sensor.
Measuring ranges can be set as desired with DIP switches and
potentiometers.
|
|
-
Measuring
ranges can be configured as desired with DIP switches and
potentiometers
-
Indication
of open-circuit sensor or short-circuit with red LED
-
Electrical
isolation between measurement input, measurement output and
auxiliary power
-
Power
supply: integrated AC-DC power pack with large tolerance range
-
Housing:
SINEAX: S17 housing for top-hat rail or wall mounting
|
|
|
|
|
Input set to 0 ... 100 °C,
output set to 4 ... 20 mA. 3-wire connection. Setting for 2-wire
connection with DIP switch S1 and additional jumper, cable resistance
of up to 50 W is possible. Additional temperature ranges from – 170
to + 800 °C can be configured with DIP switches, fine balancing with
“Zero” and “Span” potentiometers.
|
| Article No. |
Input |
Output |
Auxiliary Power |
| SINEAX Standard variants with 1 input and 1 output |
| 602-11121010 |
0..100°C |
0 / 4.. 20mA |
24.. 60 V AC/DC |
| 602-11221010 |
85.. 230 V AC/DC |
| SINEAX with 2 inputs and 2 outputs |
| 602-12121010 |
0..100°C |
0 / 4.. 20mA |
24.. 60 V AC/DC |
| 602-12221010 |
85.. 230 V AC/DC |
|
|
|