SINEAX
UNIVERSAL AND TEMPERATURE TRANSMITTERS |
|
|
|
SINEAX V 608 DIN
MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX
V 608 Programmable Two-wire Temperature Transmitter for RTD and TC
Inputs
|
|
|
SINEAX V 608 is
a two-wire temperature transmitter. It is designed for measuring
temperature in combination with thermocouples or resistance
thermometers. Thermocouple non-linearities are automatically
compensated. The output signal is a current in the range 4
20 mA.
The input variable and measuring range are programmed with the aid of
a PC and the corresponding software.
The sensor circuit is monitored for open and short-circuits and the
output responds in a defined manner if one is detected.
The power supply (12
30 V DC) is connected together with the signal
by the two leads connected to the measurement output (loop powered).
|
|
INPUT: Thermocouple,
RTD
|
OUTPUT: 4 to 20 mA
|
|
|
|
-
Two-wire
temperature transmitter for installation in the process
environment
-
Open
and short-circuit sensor circuit supervision / Defined output
response should the supervision pick up
-
Programmable
with or without power supply connection
-
Compact
design / Makes maximum use of available space
-
Available
in type of protection "Intrinsic safety" EEx ia IIC T6
(see: Data on explosion protection")
|
|
|
|
|
|
Temperatures with
resistance thermometers for two-, three- or four-wire
connection
Pt 100, IEC 60 751
Ni 100, DIN 43 760
|
Temperatures with
thermocouples
Type B, E, J, K, N,
R, S, T acc. to IEC 60 584-1
Type L and U, DIN 43 710
Type W5 Re/W26 Re,
Type W3 Re/W25 Re acc. to ASTM E 988-90 |
|
|
|
|
SINEAX
V 611 DIN MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX V 611 Ultra-Slim Programmable
Temperature Transmitter
|
|
|
The programmable SINEAX
V 611 is a two-wire temperature transmitter.
It is used for measuring temperature in conjunction with a
thermocouple or resistance thermometer.
Thermocouple nonlinearities are automatically compensated.
The output
signal is a current in the range 4
20 mA. Measured variable,
measuring range, signaling and other parameters are programmed with
the aid of a PC and the corresponding software.
The sensor circuit is monitored for open and short-circuits and the
output responds in a defined manner if one is detected. The power
supply of 12
30 V DC is connected together with the signal by the
two leads connected to the measurement output (loop powered).
|
|
INPUT: Thermocouple,
RTD
|
OUTPUT: 4 to 20 mA
|
|
|
|
-
PC
Programmable temperature transmitter
-
Reverse
Output Capable (20-4 mA)
-
Input
Linearization
-
Non-Isolated
-
Internal
or External CJC
-
Supply
Voltage:12-30 VDC from Output Loop
|
|
|
|
|
|
|
|
Measuring input:
Measuring range:
Measuring output:
Open-circuit supervision:
Mains ripple suppression: |
Pt 100 for three-wire
connection
0
600 °C
4
20 mA
Output 21.6 mA
For frequency 50 Hz |
|
|
|
|
SINEAX
V 624 DIN MOUNT TEMPERATURE TRANSMITTER
|
|
|
|
SINEAX
V 624 Programmable Two-wire Temperature Transmitter for RTD and TC
Inputs
|
|
|
SINEAX V 624 temperature
transmitter is designed for measuring temperature in
combination with thermocouples or resistance thermometers.
Thermocouple non-linearities are automatically compensated.
The analogue output signal is either an impressed current or
superimposed voltage which is linearly proportional to temperature and
can be processed by other devices for purposes of displaying,
recording and/or regulating a constant.
The input variable and measuring range are programmed with the aid of
a PC and the corresponding software. The sensor circuit is monitored
for open and short-circuits and the output responds in a defined
manner if one is detected. The transmitter fulfils all the important
requirements and regulations concerning electromagnetic compatibility EMC
and Safety (IEC 1010 resp. EN 61 010).
It was developed and is manufactured and tested in strict accordance
with the quality assurance standard ISO 9001. ±
|
|
INPUT:
Thermocouple,
RTD
Thermistor, Custom
|
OUTPUT: 0-2 mA to 0-20 mA, 20-0
mA
0-1 V to 0-10 V, 10-0 V
|
|
|
|
-
PC
Programmable temperature transmitter
-
Reverse
Output Programmable
-
Custom
Input Linearization
-
Programmable
Sensor Fault Response
-
Removable
Plugs
-
Non-Isolated
-
3.7kV
Input, Output,
Power Isolation
-
Supply
Voltage:20 - 60 or 85 - 230 VAC VDC
|
|
|
|
|
|
|
|
Temperatures with resistance
thermometers for two-, three- or four-wire connection
Pt 100, IEC 60 751
Ni 100, DIN 43 760
|
Temperatures with
thermocouples
Type B, E, J, K, N, R, S, T
acc. to IEC 60 584-1
Type L and U, DIN 43 710
Type W5 Re/W26 Re,
Type W3 Re/W25 Re acc. to ASTM E 988-90 |
|
|
|
SINEAX V 604 DIN MOUNT
PROGRAMMABLE UNIVERSAL TRANSMITTER |
|
|
SINEAX
V 604 Programmable universal transmitter for DC currents or voltages,
temperature sensors, remote sensors or potentiometers |
|
The universal temperature
transmitter SINEAX V 604 converts the input variable a DC
current or voltage, or a signal from a thermocouple, resistance
thermometer, remote sensor or potentiometer to a proportional
analogue output signal. The analogue output signal is either an
impressed current or superimposed voltage which is processed by other
devices for purposes
of displaying, recording and/or regulating a constant. A considerable
number of measuring ranges including bipolar or spread ranges are
available. Input variable and measuring range are programmed with the
aid of a PC and the corresponding software.
Other parameters relating to
specific input variable data, the analogue output signal, the
transmission mode, the operating sense and the open-circuit sensor
supervision can also be programmed.
The open-circuit sensor supervision
is in operation when the SINEAX
V 604 is used in conjunction with a thermocouple, resistance
thermometer, remote sensor or potentiometer. The transmitter fulfils all
the important requirements and regulations concerning electromagnetic
compatibility EMC and Safety (IEC 1010 resp. EN 61 010).
It was developed and is manufactured and tested in strict accordance
with the quality assurance standard
ISO 9001. Production QA is also certified according to guideline
94/9/EG.
|
INPUT: 0-2 mV to ±40 V
0-80 ΅A to 50-100 mA
Thermocouple, RTD,
Thermistor, Potentiometer |
OUTPUT: 0-5 mA to ±40 mA
0-4 V to 12-+15 V |
|
|

|
-
PC
Programmable
-
Unipolar
or Bipolar Input and Output
-
Reverse
Output Programmable
-
Custom
Input Linearization
-
Programmable
Alarm Relay
-
3.7kV
Input, Output,
Power Isolation
-
Supply
Voltage:20 - 60 or 85 - 230 VAC VDC
|
|
|
|
|
-
Input variable
(temperature, variation of resistance, DC signal) and measuring
range programmed using PC / Simplifies project planning and
engineering (the final measuring range can be determined during
commissioning). Short delivery times and low stocking levels
-
Analogue output signal
also programmed on the PC (impressed current or superimposed voltage
for all ranges between 20 and + 20 mA DC resp. 12 and + 15 V
DC) / Universally applicable. Short delivery times and low stocking
levels
-
Electric insulation
between measured variable, analogue output signal and power supply /
Safe isolation acc. to EN 61 010
-
Wide power supply
tolerance / Only two operating voltage ranges between 20 and a
maximum of 264 V DC/AC
-
Available in type of
protection "Intrinsic safety" [EEx ia] IIC (see Data on
explosion protection")
-
Ex devices also directly
programmable on site / No supplementary Ex interface needed
-
Standard version as per
Germanischer Lloyd
-
Provision for either
snapping the transmitter onto top-hat rails or securing it with
screws to a wall or panel
-
Housing only 17.5 mm
wide (size S17 housing) / Low space requirement
-
Other programmable
parameters: specific measured variable data (e.g. two, three or
four-wire connection for resistance thermometers,
"internal" or "external" cold junction
compensation of thermocouples etc.), transmission mode (special
linearized characteristic or characteristic determined by a
mathematical relationship, e.g. output signal = f (measured
variable)), operating sense (output signal directly or inversely
proportional to the measured variable) and open-circuit sensor
supervision (output signal assumes fixed preset value between 10
and 110%, supplementary output contact signalling relay).
Highly
flexible solutions for measurement problems
-
All programming
operations by IBM XT, AT or compatible PC running the
self-explanatory, menu-controlled programming software, if
necessary, during operation No ancillary hand-held terminals needed
-
Digital measured
variable data available at the programming interface
Simplifies commissioning, measured variable and signals can be
viewed on PC in the field
-
Standard software
includes functional test program. No external simulator or signal
injection necessary
-
Self-monitoring function
and continuously running test program
Automatic signaling of defects and device failure
|
|
Measured variables |
Measuring ranges |
| Limits |
Min. span |
Max. span |
|
DC voltages
direct input
via potential divider |
± 300 mV
± 40 V |
2 mV
300 mV |
300 mV
40 V |
|
DC currents
low current range
high current range |
± 12 mA
50 to + 100 mA |
0.08 mA
0.75 mA |
12 mA
100 mA |
|
Temperature monitored
by two, three or four-wire
resistance thermometers
low
resistance range
high
resistance range |
200 to 850 °C
0...740 ohm
0...5000 ohm
|
8 ohm
40ohm |
740ohm
5000ohm |
|
Temperature monitored
by thermocouples |
270 to
1820°C |
2 mV |
300 mV |
|
Variation of
resistance
of remote sensors /
potentiometers
low
resistance range
high
resistance range |
0...740 ohm
0...5000 ohm |
8 ohm
40 ohm |
740 ohm
5000 ohm |
|
|
|
SINEAX VC 603 DIN MOUNT
UNIVERSAL TRANSMITTER WITH ALARMS |
|
|
SINEAX
VC 603 Programmable combined transmitter alarm unit for DC currents or
voltages, temperature sensors, remote sensors or potentiometers |
|
The combined transmitter
alarm unit SINEAX VC 603 converts the input variable a DC
current or voltage, or a signal from a thermo-couple, resistance
thermometer, remote sensor or potentiometer to a proportional
analogue output signal. It is also equipped with 2 limit contacts for
monitoring the input variable. The analogue output signal is either an
impressed current or superimposed voltage which is processed by other
devices for purposes of displaying, recording and/or regulating a
constant.
The binary output signals of the two limit contact circuits are used for
signaling out-of-limit conditions, control purposes and two-point
regulation.
A considerable number of measuring ranges including bipolar
or spread ranges are available.
Input variable and measuring range are programmed with the aid of a PC
and the corresponding software. Other parameters relating to specific
input variable data, the analogue output signal, the transmission mode,
the operating sense, the binary output signals and the open-circuit
sensor supervision can also be programmed. The open-circuit sensor
supervision is in operation when the SINEAX VC 603 is used in
conjunction with a thermo-couple, resistance thermometer, remote sensor
or potentiometer.
The transmitter alarm unit fulfils all the important requirements and
regulations concerning electromagnetic compatibility EMC and Safety
(IEC 1010 resp. EN 61 010).
It was developed and is manufactured and tested in strict accordance
with the quality assurance standard ISO 9001/ EN 29 001.
Production QA is also certified according to guideline 94/9/EG.
|
INPUT: 0-2
mV to ±40 V
0-80 ΅A to 50-100 mA
Thermocouple, RTD,
Thermistor, Potentiometer |
OUTPUT: 0-5
mA to ±40 mA
0-4 V to
12-15 V
1 DPDT, 2 SPDT |
|
|

|
-
PC
Programmable
-
3
Independently Configurable Alarm Contacts
-
Unipolar
or bipolar Input and Output
-
Reverse
Output Programmable
-
Custom
Input Linearization
-
3.7kV
Input, Output,
Power Isolation
-
Supply
Voltage:20 - 60 or 85 - 230 VAC VDC
|
|
|
|
|
|
-
Input variable
(temperature, variation of resistance, DC signal) and measuring
range programmed using PC / Simplifies project planning and
engineering (the final measuring range can be determined during
commissioning). Short delivery times and low stocking levels
-
Analogue output signal
and binary output signals also programmed on the PC (analogue:
impressed current or superimposed voltage for all ranges between
20 and + 20 mA DC
resp. 12 and + 15 V DC; binary: various
functions associated with the limit contact circuits) / Universally
applicable. Short delivery times and low stocking levels
-
Electrical insulation
between measured variable, analogue output signal, binary output
signals and power supply / Safe isolation acc. to EN 61 010
-
Wide power supply
tolerance / Only two operating voltage ranges between 20 and a
maximum of 264 V DC/AC
-
Available in type of
protection "Intrinsic safety" [EEx ia] IIC (see Data on
explosion protection")
-
Ex devices also directly
programmable on site / No supplementary Ex interface needed
-
Standard version as per
Germanischer Lloyd
-
Provision for either
snapping the transmitter/alarm unit onto top-hat rails or securing
it with screws to a wall or panel
-
Other programmable
parameters: specific measured variable data (e.g. two, three or
four-wire connection for resistance thermometers,
"internal" or external" cold junction compensation of
thermo-couples etc.), transmission mode (special linearised
characteristic or characteristic determined by a mathematical
relationship, e.g. output signal = f (measured variable)),
operating sense (output signal directly or inversely proportional to
the measured variable) and open-circuit sensor supervision (output
signal assumes fixed preset value between 10 and 110%,
supplementary output contact signaling relay) / Highly flexible
solutions for measurement problems
-
All programming
operations by IBM XT, AT or compatible PC running the
self-explanatory, menu-controlled programming software, if necessary
during operation / No ancillary hand-held terminals needed
-
Digital measured
variable data available at the programming interface / Simplifies
commissioning, measured variable and signals can be viewed on PC in
the field
-
Standard software
includes functional test program / No external simulator or signal
injection necessary
-
Self-monitoring function
and continuously running test program / Automatic signaling of
defects and device failure
|
|
Measured variables |
Measuring ranges |
| Limits |
Min. span |
Max. span |
|
DC voltages
direct input
via potential divider |
± 300 mV
± 40 V |
2 mV
300 mV |
300 mV
40 V |
|
DC currents
low current range
high current range |
± 12 mA
50 to + 100 mA |
0.08 mA
0.75 mA |
12 mA
100 mA |
|
Temperature monitored
by two, three or four-wire
resistance thermometers
low
resistance range
high
resistance range |
200 to 850 °C
0...740 ohm
0...5000 ohm
|
8 ohm
40ohm |
740ohm
5000ohm |
|
Temperature monitored
by thermocouples |
270 to
1820°C |
2 mV |
300 mV |
|
Variation of
resistance
of remote sensors /
potentiometers
low
resistance range
high
resistance range |
0...740 ohm
0...5000 ohm |
8 ohm
40 ohm |
740 ohm
5000 ohm |
|
|
|
|
SINEAX C 402 DIN MOUNT
ALARM UNIT |
|
|
|
SINEAX C 402 DIN Mount Alarm
Unit |
|
|
The alarm unit SINEAX
C402 is normally applied to monitor the limits of both current and
voltage measurements. The status of the device is signalled remotely by
a relay and locally by LEDs.
The electrical insulation between input, output relay contacts and the
power supply conforms to
IEC 1010. The value detected by the alarm unit is set on a potentiometer
and measured at test sockets on the front of the unit. The alarm unit
fulfils all the important requirements and regulations concerning
electromagnetic compatibility EMC and Safety (IEC 1010
resp. EN 61 010). It was developed and is manufactured and tested in
strict accordance with the quality assurance standard ISO 9001/
EN 29 001.
Production QA is also certified according to guideline 94/9/EG.
|
|

|
- 2 limit contact devices
- 2 relay outputs, each
equipped with one
changeover contact
- Signal flow direction
can be selected for relays and LEDs with jumpers
- Electrical isolation
between measurement input, contact outputs and auxiliary power
- Power supply: integrated
AC-DC power pack with large tolerance range
- Housing:
SINEAX: S17 housing for top-hat rail or wall mounting
SIRAX: B17 housing for plug-in installation to BP902 rack
|
|
|
|
|