DUAL MICROPROCESSOR
PROCESS CONTROL INDICATOR WITH THRESHOLDS |
|
|
|
DO9404 Dual Microprocessor Controlled
Indicator with Thresholds
|
|
|
DO 9404 Dual Regulator Controller Indicator with serial output
RS232. Two Channels.
The dual regulating indicator DO 9404 is a microprocessor controlled panel
instrument
with LED 96x96, with thresholds and alarms that may be
programmed and configured by the user.
In the two input channels it accepts
signals coming from two distinct transmitters or from a double
transmitter.
The transmitters may be passive with 2 wires or active with 3
wires, in voltage 0÷1 V, 0÷5 V, 0÷10 V or current 0÷20 mA; 4÷20 mA.
For both input channels the
configuration possibility is always present in the instrument, no extra
cards are needed.
|

DO 9404 Dual Indicator Controller |
The
choice of configurations for the input signals is made on the keyboard
located on the front of the instrument.
The DO 9404 Dual
Indicator Controller is provided with a serial output RS232C, the
baud rate may be configured by means of the keyboard, the control is
bi-directional and the output connector is a SUB D female 9-pole connector.
The instrument dimensions are in accordance with DIN
45700, 96x96 mm, depth 120 mm.
|
|
|
For price and info please email sales@hotektech.com
or call 253-927-6186 |
|
Related
Instruments |
Controllers,
Humidity, Pressure, Temperature
Conditioners
Isolation Amplifiers
Regulators
Signal Isolators, Conditioners,
Splitters
Transmitters,
Current, Voltage, Power, Temperature, Humidity
Thermostats |
|
|
The operating mode of the DO 9404 is chosen according to
the application, configuring the instrument with the keyboard. It is
possible to configure the instrument on the field with maximum simplicity to
adapt it to changes in the process requirements.
The configuration possibility concerns the inputs, the
extent of the scales, the set points, the alarms and the baud rate.
|
Applications
A typical application of the DO 9404
Dual Indicator Controller is the display and
regulation of signals arriving from passive 2-wire or active 3-wire
transmitters, of any physical quantity: temperature, humidity, pressure,
speed, level, etc. for a wide variety of industrial sectors and automation.
Characteristics
Set point may be configured from -9999 to +19999
Indication with 1/2" red LED's Separate terminal for each channel for voltage input 0 ÷
10 V and current input 0÷ 20 mA, 4÷ 20 mA On the terminal board an auxiliary power supply is
available at -5 Vdc max. 10 mA and +15 Vdc non-stabilized max. 44 mA for the
possible feeding of passive 2-wire transmitters. Instrument accuracy ±0. 1 % Rdg ± 1 digit A/D converter resolution: 0.05 mV/digit, 1 uA/digit Functions: Two relays with insulated HI LO exchange
contact for channel 1: RL1, RL2 Two relays with insulated HI LO exchange contact for
channel 2: RL4, RL5 One relay for the overall maximum and minimum alarms: RL3
Resistive 3A/230 Vac relay contacts
Instrument working temperature: (electronic components)
-5..+5O°C Power supply: 12÷24 ±10% Vac/Vdc.
|