CONDUCTIVITY TRANSMITTERS
|
|
|
DO9766T-R1
Conductivity transmitter for use on the field in a 122x120x57 housing
with dual LCD (measurement+ temperature), output 4...20mA. The cell
constant, the range and the temperature coefficient are completely
configurable. 2 wire passive transmitter or 4 wire active transmitter.
Power supply in active function 24Vac, on request 230Vac, in passive
function 10...35Vdc.
DO9786T-R1: Panel mounting conductivity transmitter in a 96x96
housing with dual LCD (measurement+ temperature), output 4...20mA. The
cell constant, the range and the temperature coefficient are completely
configurable. 2 wire passive transmitter or 4 wire active transmitter.
Power supply in active function 24Vac, on request 230Vac, in passive
function 10...35Vdc.
|
DO9786T-R1 DO9766T-R1Conductivity transmitters |
| Our
Price: |
Contact us for
pricing |
| Phone:
|
253-927-6186
866-318-6186 |
| Fax:
|
253-927-6189 |
| email:
|
sales@hotektech.com |
|
|
|
|
|
|
|
DO9786T-R1 DO9766T-R1Conductivity transmitters convert the output of a conductivity electrode
into a signal,
with temperature compensation,
at 4÷20 mA.
The electrode input circuit is
galvanically insulated
against the 4÷20 mA output signal. An LCD indicator
allows viewing of the process
signal value and of the various parameters.
The accurate design and choice of components
make the instrument precise and
reliable for a long working life. The instrument works in conjunction
with a
conductivity electrode and a temperature probe (Pt 100 sensor, 100 ohm at 0°C).
|
CONDUCTIVITY
INPUT Measuring range 0.0199.9 mS 2/4 electrodes Configurable cell constant 0.01...199.9 cm Transducer energizing Square wave 10...1000 mV, depending on conductivity,
200...1600 Hz, depending on conductivity Input impedance >100 Mohm Cable length < 10 meters unscreened <50 meters screened (about 2 nF) Accuracy 0.5% of reading ±2 digits ±0.01% per °C of drift in temperature
TEMPERATURE INPUT Pt100 2/4 wire s -50...199.9°C Transducer energizing 0.5 mA DC Cable length < 10 meters unscreened <50 meters screened (about 5 nF) Accuracy 0.2°C ±0.1% of reading ±0.01°C/°C of drift in temperature
TEMPERATURE COMPENSATION None
Manual: Linear 0.00 4.00%/°C -50...+200°C Automatic: Linear 0.00 4.00%/°C -50...+200°C Reference temperature: 20 or 25°C Configurable
CURRENT OUTPUT 4.00...20.00 ma: Programmable and proportional to
conductivity Accuracy 0.5% of reading ±0.02 mA Insulation: 2500 VAC 1 minute
RELAY OUTPUT A and B: Bistable, contact 3A/230 VAC free potential
POWER SUPPLY Passive: 4÷20 mA, 2 wire configuration, 10÷35 V Active: 24/230 VAC - 15/+10%, 1 VA, 48...62 Hz, DO 9766T Container:
120x 1 22x56 mm, Protection class IP64 DO 9786: Container: 96x96x126 mm. Protection class IP44
|
CE CONFORMITY
Safety: EN61000-4-2, EN61 010-1 level 3 Electrostatic discharge: EN61000-4-2 level 3 Fast electric transients: EN61000-4-4 level 3 Energy impulse: EN61000-4-5 level 3 Voltage variation: EN61000-4-11 level 3 Susceptibility to electromagnetic interference:
IEC1000-4-3 Emission of electromagnetic interference: EN55020 class B
|
ORDER CODE:
DO 9786T: Conductivity transmitter 4÷20 mA passive or
active, power supply 24 VAC with double display 96x96 mm, for panel
mounting. DO 9766T: Conductivity transmitter 4÷20 mA passive or active, power supply
24 Vac with double display 122x120 mm, for use on the field. HD 882 M100/300: Temperature probe with Pt100 sensor, miniature head,
shaft
06x300 mm. HD 882 M 100/600: Temperature probe with Pt100 sensor, miniature head,
shaft 06x600 mm. HD 8712: Calibration solution 0.1 mol/l corresponding to 12,880 uS/cm at 25°C.
HD 8714: Calibration solution 0.01 mol/l corresponding to 1413 uS/cm at 25°C.
|