  Test measurement instrumens. Analytical instruments, ph meters, dissolved oxygen meter, hygrometer, salinity meter, weather instruments. Power analyzers, Gas combustion analyzer, Electronic load, Harmonic analyzer. Pressure calibrator, deadweight tester, temperature calibrator, current loop calibrator. Temperature datalogger, humidity datalogger, barometric pressure datalogger, wireless datalogger. Hygrometer, humidity datalogger, HVAC instrument, humidity controllers transmitters. Candela meter, Luminance meter, Radiometer, Albedometer, Luminance transmitter. Cable detectors, coil tester, insulation resistance, resistance bridge, tachometers. Digital multimeter, clamp on meter, amperometer, current meter, high line voltmeter, phasing sequence meter.  
  Resistance bridge, ohmmeter, insulation resistance meter, multimeters, milli ohmmeter, micro ohmmeter, megohmmeter. Manometer, Pressure gauge, deadweight tester, pressure pump, vacuum pump, pressure calibrator. Simulator, Calibrator, resistance standard, resistor decade, inductance standard, thermometry standards. Thermometry bridge, precision thermometer, infrared thermometer, temperature calibrator, dry block calibrator. Current transmitter, Luminance transmitter, energy transmitter, pressure transmitter, temperature transmitter.  
 

Search  

 
 
 

DIGITAL TEMPERATURE CONTROLLER REGULATOR


HD4034 Digital LED ON/OFF temperature regulator 48x78. Pt100 sensor.
Measuring range -50°C…+150°C. Resolution 0,1°C.
Hysteresis 0.6...6°C. Relays 5A 220V resistive. Power supply 24Vac/dc, on request 110….230Vac/dc.



Temperature controller regulator thermostat
Our Price: Contact us for pricing
Phone: 253-927-6186
866-318-6186
Fax: 253-927-6189
email: sales@hotektech.com

The HD 4034 temperature controller regulator thermostat is an ON/OFF regulator with relay output
(1 exchange contact 3A/22OV). 
The setting of the intervention temperature (set point) is carried out by pressing the button on the left of the front panel of the instrument and turning the knob on the right until the temperature at which the relay contact is to open is shown on the display. Intervention hysteresis may be adjusted with a trimmer at the rear of the instrument.

The temperature sensor is a PT 100 probe. If this is connected with 2 wires and a cable with a section of 1 mm2 , a reading in excess of 0.006°C/m is obtained. 
For long distances we advise a three-wire connection, with the third wire connected to terminal 2.
With the three-wire connection the line resistance is automatically compensated.
The thermostat may be used either for heating or for cooling, simply by moving the jumper at the rear of the instrument. 
When the jumper is in HEATING position, the relay is energized if the probe temperature is lower than the set temperature; when the jumper is in COOLING position, the relay is energized if the probe temperature is higher than the set temperature.

TECHNICAL DATA

Using range: -50°C ...+150°C
Resolution: 0.1°C
Display: LED, height 12.7 mm
Precision: ±0.2°C ±0.1% of reading
Connection: with 2 or 3 wires, PT 100 sensor
Power supply: 24 Vac / 3VA
Output: relay contact 3A/22OV

Set point setting: with a button on the front panel
Hysteresis: 0.6 ... 6°C adjustment with a 1 -turn trimmer at the rear of the instrument
Working temperature: -5°C ... +45°C
Dimensions: front panel 78 x 48 mm instrument body 72 x 42 x 78 mm

 