Toll Free: 866-436-2430                     Email: sales@hotektech.com

 
 
Instruments, calibrators, standards, analyzers, dataloggers. analyzers
 
  Test measurement instrumens. Analytical instruments, ph meters, dissolved oxygen meter, hygrometer, salinity meter, weather instruments. Power analyzers, Gas combustion analyzer, Electronic load, Harmonic analyzer. Pressure calibrator, deadweight tester, temperature calibrator, current loop calibrator. Temperature datalogger, humidity datalogger, barometric pressure datalogger, wireless datalogger. Hygrometer, humidity datalogger, HVAC instrument, humidity controllers transmitters. Candela meter, Luminance meter, Radiometer, Albedometer, Luminance transmitter. Cable detectors, coil tester, insulation resistance, resistance bridge, tachometers. Digital multimeter, clamp on meter, amperometer, current meter, high line voltmeter, phasing sequence meter.  
  Resistance bridge, ohmmeter, insulation resistance meter, multimeters, milli ohmmeter, micro ohmmeter, megohmmeter. Manometer, Pressure gauge, deadweight tester, pressure pump, vacuum pump, pressure calibrator. Simulator, Calibrator, resistance standard, resistor decade, inductance standard, thermometry standards. Thermometry bridge, precision thermometer, infrared thermometer, temperature calibrator, dry block calibrator. Current transmitter, Luminance transmitter, energy transmitter, pressure transmitter, temperature transmitter.  
 

Search  

 
 
 

MODULAR TEMPERATURE TRANSMITTER


HD688 T Temperature transmitter 4...20mA, 0…20mA, 0…10Vdc for Pt100 sensor with 3-way galvanic separation 3000V. Power supply 12...24Vdc/ac. DIN 2 modules container (35 mm) with rail attachment 35 mm. Five working ranges may be configured by means of a jumper:
(-50°C..+50°C); (0°C..+50°C); (0°C..+100°C); (0°C..+200°C); (0°C..+400°C).

The Temperature transmitter converts the signal coming from a Pt100 sensor into an analogue signal that can be selected by a Jumper among these values: 0÷20mA, 4÷20mA, 0÷10V. The signal is galvanically separated among input, output and power supply. The transmitter is built into a two-module DIN container for 35 mm asymmetric guide..



TEMPERATURE TRANSMITTER
Our Price: Contact us for pricing
Phone: 253-927-6186
866-318-6186
Fax: 253-927-6189
email: sales@hotektech.com

Output analogue signal: 0÷20 mA,  4÷20 mA, 0÷10 Vdc

The HD 688T transmitter is built inside a 2-module DIN box for 35 mm asymmetric guide.
The module turns the signal coming from a Pt100 into an analogue signal that can be sorted out through a jumper connection between 0÷20 mA, 4÷20 mA, 0÷10 V. 

The signal is galvanically separated among input, output and power supply. 
The 3-way insulation of the module allows the prevention of reciprocal influences in the
presence of various measuring circuits.

The HD 688T Temperature Transmitter is made up of the following stages:
- input stage including linearization of the curves and equalization of the resistance of the line
cable (3 wires) of Pt100, conversion from voltage into frequency;
- universal output stage through jumper connection, conversion from frequency into voltage;
- power supply stage.
The configuration of the measuring range or the output signal can be modified at any time, an outstanding feature being that any variation does not involve the need to calibrate the transmitter again.

Principal characteristics:
- Galvanic separation among input, output   and power supply
- Pt100 Platinum probe
- Insulation: 3kV at 50Hz for 1 minute
- Scale configurations

Supply voltage
Output
Full scale
DRIFT
MAX
load
Measuring
Range
Measuring
current
12÷24V@±10%,
65mA
0÷10Vdc
0÷20mA
4÷20mA
0,02%/°C 5mA
500 Ω
500 Ω
-50...+50°C
0...+50°C
0...+100°C
0...+200°C
0...+400°C
1mA

Please email sales@hotektech.com or call 253-927-6186 if you are interested in a purchase, or
  need additional information.