Signal isolator
|
-
Loop Powered
Isolator with Power Transfer
-
Single and
Multi-Channel Versions
-
Intrinsically Safe
Versions
DC signal isolator,
housing N17, 1 channel or 2 channel
with power supply transfer, also available for FSK
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX DCM 817 Signal Isolator for PCB Mounting
|
|
|
SINEAX DCM 817
Passive DC signal isolator without power supply, modular design.
The signal isolator serves to electrically insulate a DC signal in
the range 0/4
20 mA.
It operates passively, i.e. it does not require a separate power
supply.
The signal isolator is available in two versions which
differ in the shape of the connection pins.
Its modular design enables one or several signal isolators to
be mounted on a printed circuit board.
Electrically insulated between input and output signal / Prevents
the transfer of interference voltages and currents, solves grounding
problems in meshed signal networks and is cheap and small
No power supply required / Less termination and wiring work
Modular design / Versatility of application
Small dimensions / Saves space
|

Signal isolator
|
- Loop Powered / 500V
Isolation
- Cost Effective OEM
Product
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX TI 816 500V Passive DC Signal Isolator for DIN-Rail
|
|
|
The Passive DC signal isolator
SINEAX
TI 816 serves to electrically insulate an analogue DC signal in
the range 0
20 mA which depending on version is then converted to a
current or voltage
signal (0
20 mA or 0
10 V).
It operates passively and does not require a separate power supply,
but derives the little auxiliary energy it needs from the DC signal.
Its narrow casing is designed for mounting on different types of
standard rails.
A number of signal isolators can be mounted immediately next to each
other and where there are many DC signals to be isolated can form a
compact isolator block.
|
Signal isolator
|
- Loop Powered with V
or mA Outputs
- Only 0.5 "
(12.5mm) Wide
The SINEAX TI 816
signal isolator electrically isolates the
analog 0 to 20 mA direct current signal, which,
depending upon
model, is converted to a current or
voltage signal (0...20 mA or 0...10 V).
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX TI 807 4kV Passive DC Signal Isolator
for
rail and wall mounting
|
|
|
The Passive Signal isolator
SINEAX
TI 807 serves to electrically insulate the analogue DC signal in
the
range 0
20 mA which depending on version is then converted to a
current or voltage
signal (0
20 mA or 0
10 V).
It operates passively and does not require a separate power supply,
but derives the little auxiliary
energy it needs from the DC signal.
The series of isolators also includes "intrinsically safe"
explosion proof versions with either an intrinsically safe input
signal [EEx ib] IIC or intrinsically safe output signal [EEx ia] IIC.
They are thus suitable for use in connection with intrinsically safe
equipment installed in the hazardous area. The signal isolator is
supplied in two different housings depending on the number of
transmitter channels to be isolated: SINEAX TI 807-5 with one
transmitter channel to be isolated in housing
Type N17 and SINEAX TI 807-1 with two or three channels in housing
Type S17.
Both types of housing are suitable for either rail or wall mounting.
|
Signal isolator
|
- Loop Powered with V
or mA Outputs
- Single and
Multi-Channel Versions
- Intrinsically Safe
Versions
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX TV 808 1-Channel Isolator Isolating Amplifier Unipolar
Bipolar
|
|
|
The purpose of the 1
Channel isolating amplifier SINEAX TV 808 is to electrically insulate
input and output signals, respectively to amplify and/or change the
signal level or type (current or voltage) of the input signals.
Electric insulation between input, output (2.3 kV) and power supply
(3.7 kV) / Prevents measurement errors due to potential leakage.
Flexibility provided by 36 different input and output combinations
selected by simply positioning plug-in jumpers / No influence on
accuracy / Reduced stocking.
Non-standard user-specific ranges available.
AC/DC power supply / Universal .
Available in type of protection "Intrinsic safety" [EEx ia]
IIC (see Data on explosion protection").
Provision for either snapping the isolating amplifier onto top-hat
rails or securing it with screws to a wall or panel.
Housing only 17,5 mm (size S17 housing) / Low space requirement.
|
Signal isolator amplifier
|
- 3.7kV Isolation
Power Supply verses I/O,
2.3kV Isolation Input to Output
- Fully Configurable
Input and Output Settings
- Zero and Span
Adjustments
- Intrinsically Safe
Versions
- Power Input:
24...60V AC/DC or 85...230V AC/DC
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX TV 808 Dual Channel Isolator Isolating Amplifier
Unipolar Bipolar
|
|
|
The purpose of the Dual
Channel Isolating Amplifier SINEAX TV 808 is to electrically insulate
input and output signals, respectively to amplify and/or change the
signal level or type (current or voltage) of the input signals.
The amplifier fulfils all the important requirements and regulations
concerning electromagnetic compatibility EMC and Safety (IEC 1010 resp.
EN 61 010).
It was developed and is manufactured and tested in strict accordance
with the quality assurance standard ISO 9001.
The device has two channels and provides two independent isolating
amplifiers in an extremely small space. The user has a wide choice of
input and output ranges and can set the desired one with the aid of
soldered jumpers and potentiometers. A version with one input and two
outputs is available that enables two electrically insulated outputs
to be obtained from a single input signal.
|
Signal isolator amplifier
|
- Dual Channel or
Signal Splitter
- 3.7kV Isolation
Power Supply verses I/O, 2.3kV
Isolation Input to Output
- Zero and Span
Adjustment for Each Channel
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX B840 4-Channel Power Pack for 2 wire transmitters
DIN-Rail Mount
|
|
|
The Four Channel Power supply unit
SINEAX B 840 provides the DC power supply for 2-wire
transmitters.
Depending on the device execution there are 2 or 4 power supply
outputs available.
Each power supply output is monitored by a green LED.
The corresponding green LED is continuously lit when the measuring /
supply circuit is closed.
|
Power Transmitter
|
- 4-Channel 4...20mA,
24V DC Loop Power Supply
- LED Monitoring of
each Channel Independently
- Isolation between
each Channel
- Supply Voltage: 24V,
115V or 230V AC 50/60Hz
- 30mA Current Limiter
for each Channel
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX B 811 Power Pack with additional functions
and Signal outputs
|
|
|
The power supply unit
SINEAX B 811 provides the DC power supply for 2-wire transmitters and
transfers the measured variable unchanged to the electrically
insulated output. Conversion to a different signal range such as 0
5
mA or 1
5 V (signal converter) is also possible.
Some versions of
the SINEAX B 811 are designed for FSK1 communication.
They are used in conjunction with "intelligent" 2-wire
transmitters which are capable of dialogue and operation according to
the FSK principle and the HART or user-specific protocol.
The series also includes "intrinsically safe" versions [EEx
ia] IIC with an intrinsically safe measurement/supply circuit. These
operate in conjunction with intrinsically safe 2-wire transmitters
located in explosion hazard areas.
Provision is made for monitoring
the measurement/supply circuit to detect short and
open-circuits.
Either of these faults is signaled by the fault signaling relay AF
and the red LED.
The output signals
A1 and A12 can be set on the DIP switches to have a linear increasing
or decreasing response.
The instrument fulfils all the important requirements and regulations
concerning electromagnetic compatibility EMC and Safety (IEC 1010 resp.
EN 61 010).
It was developed and is manufactured and tested in strict accordance
with the quality assurance standard ISO 9001.
Production QA is also certified according to guideline 94/9/EG.
|
|
- Isolation between
Inputs, Outputs and Power Supply: 3.7kV
- Intrinsically Safe
Versions
The SINEAX
B 811 power supply provides 2-wire measuring transducers with DC power
and forwards the measuring
signal at a ratio of 1:1 to the measurement
output in an
electrically isolated fashion.
Conversion to other signal ranges is also possible,
for example
0...5 mA or 1 to 5 V (signal transducer).
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX TV809 Programmable Isolating amplifier, 1 Channel
|
|
|
The purpose of the
Programmable Isolating amplifier SINEAX TV 809 is to electrically insulate
input and output signals, respectively to amplify and/or change the
signal level or type (current or voltage) of the input signals.
Measured variables and measuring ranges are programmed with the aid of
a PC, a programming cable and the programming software.
Specific measured variable data such as analogue output signal,
transmission characteristics and various functions in combination with
the alarm function can also be programmed.
The isolating amplifier
fulfils all the important requirements and regulations concerning
electromagnetic compatibility EMC and Safety (IEC 1010
resp. EN 61 010). It was developed and is manufactured and tested in
strict accordance with the quality assurance standard ISO
9001/EN 29001.
An explosion-proof "intrinsically safe" [EEx ia] IIC version
rounds off this series of SINEAX TV 809.
|
Isolating Amplifier
|
- Isolation Amplifier
- Voltage Input Ranges
from 0...30mV to 0...1000V DC (2000V Span with Bipolar Input)
- Current Input Ranges
from 0...220ľA to 0...100mA
- Unipolar or Bipolar
Input and Output values
- 57 point
linearization table for complete configuration of inputs
- Programmable Relay
Alarm
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX TV819 One Channel Isolating Amplifier Unipolar Bipolar
|
|
|
The purpose of the One
Channel Active Isolating Amplifier SINEAX TV 819 is to electrically insulate
input and output signals, respectively to amplify and/or change the
signal level or type (current or voltage) of the input signals.
The compact SINEAX TV 819 provides a large selection of input and
output ranges that can be configured by the user with soldered jumpers
and potentiometers.
The amplifier fulfils all the important requirements and regulations
concerning electromagnetic compatibility EMC and Safety (IEC
1010 resp. EN 61 010). It was developed and is manufactured
and tested in strict accordance with the quality assurance standard
ISO 9001.
|
Isolating Amplifier
|
- Isolation Amplifier
- Voltage Input Ranges
from 0...30mV to 0...1000V DC
(2000V Span with Bipolar Input)
- Current Input Ranges
from 0...220ľA to 0...100mA
- Unipolar or Bipolar
Input and Output values
Isolating
amplifier for electrically insulating,
amplifying and
converting DC signals, input and
output ranges
adjustable with soldered jumpers and
potentiometers.
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX V 604 Programmable Universal Transmitter
DC current voltage, temperature sensor
|
|
|
The universal programmable
universal transmitter SINEAX
V 604 converts the input variable a DC current or voltage, or
a signal from a thermocouple, resistance thermometer, remote sensor or
potentiometer to a proportional analogue output signal.
The analogue output signal is either an impressed current or
superimposed voltage which is processed by other devices for purposes
of displaying, recording and/or regulating a constant.
A considerable number of measuring ranges including bipolar or spread
ranges are available. Input variable and measuring range are
programmed with the aid of a PC and the corresponding software. Other
parameters relating to specific input variable data, the analogue
output signal, the transmission mode, the operating sense and the
open-circuit sensor supervision can also be programmed.
The open-circuit sensor supervision is in operation when the SINEAX V
604 is used in conjunction with a thermocouple, resistance
thermometer, remote sensor or potentiometer.
The transmitter fulfils
all the important requirements and regulations concerning
electromagnetic compatibility EMC and Safety (IEC 1010
resp. EN 61 010).
It was developed and is manufactured and tested in
strict accordance with the quality assurance standard ISO
9001.
Production QA is also certified according to guideline 94/9/EG.
|
Current Voltage Transmitter |
- Inputs: mV/V, mA, TC,
RTD, W
- Wide Range of
Outputs
- Isolation between
Inputs, Outputs and Power Supply: 3.7kV
- Fully Configurable
Relay Contact
- Intrinsically Safe
Versions
The SINEAX V 604
universal measuring transducer
converts the measured quantity - a
direct current, a direct
voltage or a signal from a thermocouple, a
resistance
thermometer, a remote sensor or a potentiometer - into an
analog, proportional output quantity.
The analog output quantity,
which can be realized in the
form of a load-independent current or
load-independent
voltage signal, can be used for display, recording
and/or
continuous control.
|
|
|
|
For
price and info please email sales@hotektech.com
or call 253-927-6186 |
|
|
SINEAX VC 603 Universal Programmable Transmitter Alarm Unit
|
|
|
The combined programmable transmitter
with alarm unit SINEAX VC 603 converts the input
variable a
DC current or voltage, or a signal from a thermo-couple, resistance
thermometer, remote sensor or potentiometer to a proportional analogue output signal. It is also equipped with 2
limit contacts for monitoring the input variable. The analogue output
signal is either an impressed current or superimposed voltage which is
processed by other devices for purposes of displaying, recording
and/or regulating a constant.
The binary output signals of the two limit contact circuits are used
for signaling out-of-limit conditions, control purposes and two-point
regulation.
A considerable number of measuring ranges including bipolar or spread
ranges are available.
Input variable and measuring range are programmed with the aid of a PC
and the corresponding software. Other parameters relating to specific
input variable data, the analogue output signal, the transmission
mode, the operating sense, the binary output signals and the
open-circuit sensor supervision can also be programmed. The
open-circuit sensor supervision is in operation when the SINEAX VC 603
is used in conjunction with a thermo-couple, resistance thermometer,
remote sensor or potentiometer.
The transmitter/alarm unit fulfils all the important requirements and
regulations concerning electromagnetic compatibility EMC and Safety (IEC
1010 resp. EN 61 010).
It was developed and is manufactured and tested in strict accordance
with the quality assurance standard ISO 9001/ EN 29 001. Production QA
is also certified according to guideline 94/9/EG.
|
Programmable Transmitter |
- Same Inputs as the
SINEAX V 604
- 3 Independently
Configurable Alarm Contacts
- Intrinsically Safe
Versions
The SINEAX VC 603
combination measuring transducer/limit
monitor converts the measured
quantity - a direct current,
a direct voltage or a signal from a thermocouple, a resistance thermometer, a remoter
sensor or a potentiometer - into an analog, proportional output
quantity.
It is also equipped with two limit contacts for monitoring the
measured quantity.
|
|
|