| INFRATEK
AG
|
|
DC SOURCE TESTER FOR STATIONARY BATTERIES |
|
|
DC Batteries Source Stationary Battery Tester |
|
|
DC Source Tester
for Stationary Batteries
|
-
Ri: 20/400/8000 mOhm
-
Ub: 30/120 Volt
-
15,5x9x3,5cm; 400gr.
-
Data storage, RS-232
|
|
|
|
For price and info please email sales@hotektech.com
or call 253-927-6186 ext. 1
|
|
|
Testing Stationary Batteries using
the MODEL 23 DC Source Tester
There are 3 possible test methods:
Method 1:
Use the 23 DC Source Tester and a label
printer. Every battery has its individual reference values printed on a
label which is attached to the battery. Every year maintenance
measurements are made and a new label is put on top of the label of the
previous year. The user can set its own limits for the increase of Ri.
In general limits of 30% to 40% increase are applied.
When these limits
are reached the battery cell or module is replaced.
|
Stationary Battery Tester
setup with Label-Printer
|
This test method is reliable and
efficient at the same time. Stationary batteries are being charged
constantly and therefore Ri is measured under the same condition from
year to year.
An increase of Ri of 30% indicates approximate 30% loss
of battery capacity.
The measured values are also stored in the tester
and can be transferred to a PC file for maintenance.
|
Method 2:
Use the 23 DC Source Tester, The PC software, a RS-232 Interface cable (max. 15m) and a notebook
computer. Every battery block is labeled N=001 to N=xxx. A 120V back-up
system, for example contains 10 battery blocks of 12V each. In this case
the blocks are numbered N=1 to N=12.
The testing proceeds as follows:
- Select the file with the reference values
for this particular battery system.
- Connect the RS-232 interface cable and start
measurement with block N=1.
The measured values are transferred to
the notebook. The measurement is right away compared to the
reference value of this block. When limits are exceeded the
maintenance person is alerted. When finished you have the whole
picture as well as a record data.
|
Method 3:
In this test method, data are not directly
transferred to the notebook. The measurements are first stored in
nonvolatile memory of the tester under N=1 to N=xxx (max. 500). When
the testing is finished the data are read into a notebook on-site or
are transferred to a PC in the office.
The supplied software gives
quick answers.
The 23 DC Source Tester can store up to 500 values of battery
blocks or cells.
This will be enough storage even for large systems.
|
|
DC Tester Models
|
| Product |
Description |
| Full Version |
MODEL 23
DC-Source Tester with RS-232 and Carrying case,
windows software, label printer, battery pack for printer,
4-wire measuring clips and RS-232 cable to PC. Weight 3kg. |
| Med Version |
MODEL 23
DC-Source Tester with RS-232 and Carrying case,
windows software, 4-wire measuring clips, RS-232 cable to PC. |
| Gen Version |
MODEL 23
DC-Source Tester without RS-232 and Carrying
case and 4-wire measuring clips. |
| Car Full |
Infratek 23
DC-Source Tester for car battery testing with RS-232 and
Carrying case, battery load, label printer and measuring clips. |
| Car |
Infratek 23
DC-Source Tester for car battery testing without RS-232 with
carrying case, battery load and measuring clips. |
|
Accessories
|
| Accessory |
Description |
| ACS1 |
Special 4-wire
measuring clips. |
| ACS2 |
USB - RS232 Adapter
cable, USB 1.1 compatible, Windows 98/2000/ME/XP, > 1Mbps data
transfer rate |
|
|
Specification
|
| Size
of Batteries |
Test
batteries 0.5Ah-2000Ah and voltages up to 120V |
sealed, non-sealed;
lead acid and other |
| Voltage
Ub |
Ranges
2; 0-30V, 0-200V
Resolution; 10mV, 0.1V
Accuracy; 1% +/- 1 digit |
200Vdc maximum
Display; 3 digits
23° +/- 3°K |
| Source
Resistance Ri |
Ranges
3; 0-20 milliohm, 0-400 milliohm, 0-8 ohm
Resolution; 0.01, 0.1 mW
Measurement repetition; +/- 1 digit
Accuracy; 1% +/- 2 digit |
Ub: 1.6V-120V
Display 3 digits
Signal max 20dB below noise
Signal max 20dB below noise |
| Display |
6.5mm,
16 character LCD |
V, milliohm, Mode |
| Interface |
RS-232,
isolated from batteries |
300V CAT II |
| Operation/Time |
Via
menu, 3 controls |
0.6s measurement
time |
| Data
Storage |
500
complete sets UB, Ri |
N=1 to N=500 |
| Supply |
9V
battery or accumulator |
for 6-8h operation |
| Size/Weight |
155
x 90 x 35mm; 400 gr. |
- |
| Temperature |
Operating:
0-30°K; storage: -10 -40°K |
- |
| Tester
versions |
Full:
Tester, printer, software
Med: Tester, software
Gen: Tester, no interface
Car: Tester including battery load
Car Full: Tester including battery load,
printer |
Stationary
batteries
Stationary batteries
Traction/Stationary batteries
Car batteries
Car batteries |
|