INFRATEK AG
PC10 SINGLE AND THREE PHASE POWER CONVERTER
Single and Three Phase Power Converter

PC10 Spectral Power Converter measures, computes and transmits all your important power variables to your computer. The software lets you select the quantities you want to display on the PC/Notebook monitor. The settings, such as auto or manual ranging are easily changed and measurements are stored at a mouse click. The Spectral Power Converter is available in single or three phase versions and combines an ammeter, voltmeter, wattmeter and a spectrum analyzer in a single light weight package.

PC10 Power Converter

Turns a PC into a Power Converter

  • Suitable for frequency inverter drivers

  • Displays up to 50 Values on your monitor

  • Harmonics analysis capability

  • DC-300kHz, 15mA-40A, 0.3V-1000V

  • Easy to use

  • Software package for Win95/98/NT

 

For price and info please email sales@hotektech.com or call 253-927-6186 ext. 1

Related Instruments Power Analyzers
Power Converters

Digital Multimeters
Clamp-On Meters

From the simultaneous and precise voltage and current measurement you can obtain the RMS, rectified mean, mean, min, max and harmonics through the 99th order. Particular care has been taken to obtain precise power readings (watts, VA, VAR and power factor) at highly distorted signals. 
Other values determined are: frequency, crest- and form factor, THD, Wh, VAh, VARh, Ah, harmonics of power, harmonics of impedance (magnitude and phase) and line-to-line voltages.

 
PC-Software

5 front panel versions

  • Pop-up menus

  • Save button

  • Graphics

 

The PC10's combination of high frequency performance, excellent common mode rejection and simultaneous measurements is needed for accurate readings on inverter drives, switched mode power supplies and ballast lighting equipment. 
The current input from 15mA to 40A can be extended to 100A with our option, or you can use your own Hall sensor for current measurements up to 20kA. A shunt input for high frequency current viewing resistors or current clamps is included. Measurement accuracy of 0.1% in a compact, light weight instrument is useful in the laboratory, in the field and in automatic test systems.

The package contains software (DOS or Windows) to control the Spectral Power Converter, read data, display data and store data. Software is available for standard applications in continuous and triggered measurement mode. 
The software for motor- and transformer testing makes use of the analog inputs to determine mechanical power, torque, speed, slip, corrected power and other values from external transducers. 
An extensive software driver for LabView is available to build a test system to your needs.

PC10 Spectral Power Converter
Product Description
PC10-1/0.1 Single Phase Power Converter, 0.1% accuracy
including RS-232 and Operating Software under Windows
PC10-1/0.05 Single Phase Power Converter, 0.05% accuracy
including RS-232 and Operating Software under Windows
PC10-3/0.1 Three Phase Power Converter, 0.1% accuracy
including RS-232 and Operating Software under Windows
PC10-3/0.05 Three Phase Power Converter, 0.05% accuracy
including RS-232 and Operating Software under Windows
Accessories
Accessory Description
ACS1 Current clamp with connector to PC10
shunt input; 0-400A, DC-1kHz, 2%
ACS3 Soft carrying case for PC10
ACS4 Set of test leads, max. 32A, 1.5m
(2 red; 2 black)
ACS5 Shunt input connector
ACS6 Service Manual PC10
ACS7 Rack Mounting Kit
ACS8 Official Calibration Certificate from
SCS (Swiss Calibration Service)
Options
Option Description
01 TTL-Input for External Synchronization (Factory installed)
02 RS-232- and IEEE-488 Interface, nonvolatile memory for IEEE-address
03 RS-232- and IEEE-488 Interface, 8 analog inputs (4 x +/-10V, 4 x +/-5V)
04 3-Phase Current Sensor Module 0-100A (supply by PC10)
05 Operating software under DOS to control PC10, read data and store data via
RS-232 interface
06 PC10 software driver for National Instrument LabView
07 Software for Motor testing
08 Software for Transformer testing
09 Network to form artificial neutral for measurements on Frequency Inverters
PC10 Specification
 
Voltage Ranges, 8 ranges 1-3-10-sequence; 0.3V, 1V, 3V, 10V, 30V, 100V, 300V, 1000V  
Frequency range DC, 0.1Hz-300kHz
Crest Factor 4:1 at 50% full scale (fs)
Input Impedance 1MΩ
Common Mode - 50Hz/100kHz 155dB/95dB
Standard accuracy 23°K ±3°K; rms, mean, rectified mean; for 0.3, 1V range, input >50% fs
1Hz-1kHz =           ±(0.1% rdg + 0.1% range)
DC, 1kHz-10kHz = ±(0.2% rdg + 0.2% range)
10kHz-100kHz =    ±(0.3% range +0.04%/kHz rdg) *
100kHz-300kHz =  ±(0.3% range + 0.04%/kHz rdg), typical
improved accuracy
±(0.05% rdg + 0.05% range )

* 0.3V range typical
Current Ranges, 11 ranges 1-3-10-sequence; 15mA,50mA,150mA,500mA,1.5A,5A; 1,3,10,30,100A  
Frequency range DC, 0.1Hz-300kHz
Crest Factor 4:1 at 50% full scale (fs)
Common Mode - 50Hz/100kHz 160dB/120dB
Standard accuracy 23°K ±3°K
1Hz-500Hz
500Hz-1kHz
DC, 1kHz-10kHz
10kHz-100kHz
100kHz-300kHz
5A-/Shunt input¹
±(0.1% rdg + 0.1% range)
±(0.1% rdg + 0.1% range)
±(0.2% rdg + 0.2% range)
±(0.3% rdg + 0.04%/kHz rdg)
±(0.3% rdg + 0.04%/kHz rdg)
30A input¹
±(0.1% rdg + 0.1% range)
±(0.3% rdg + 0.2% range)
±(0.9% rdg + 0.2% range)
±(0.3% rdg + 0.5%/kHz rdg)¹
,typical
improved accuracy 1Hz-400Hz
±(0.05% rdg + 0.05% range)

DC typical
¹for 2 lowest ranges, input
>50% fs
Power 80 Ranges corresponding to the products V x A  
Frequency range DC, 0.1Hz-300kHz
Accuracy 23°K ±3°K
1Hz-1kHz                 Add accuracy percentage figures of current and voltage
DC, 1kHz-10kHz       input and add 0.04%/kHz of Vrms x Arms / PF
10kHz-100kHz

PF = 0 to ±1
PF = 0 to ±1
PF = 1
Frequency 0.1Hz-300kHz, A or V triggered; Accuracy ±0.1%  
Computed Values Accuracy; Reactive Power, Var = ±(VA² - W²)½; Apparent Power: VA = Arms Vrms;
Power Factor: PF = W/VA; Crest Factor: CF = Ap/Arms, Vp/Vrms; Form Factor:
FF = At/Arms, Vt/Vrms; Impedance: Z = Vrms/Arms;
Total Harm Dist: THD = (Irms² - IFund²)½/Irms
Add accuracy percentage
figures of values involved
in computation.
Integrator Energy, Charge; Accuracy - Wh, VAh, Varh, Ah; Basic accuracy of integrated quantity.  
Harmonic Analysis Frequency range of fundamental - 2.5Hz-100kHz  
Range of harmonic 1-99
Accuracy, Harmonic current and voltage
2Hz-1kHz =        ±(0.2% rdg + 0.1% range)
1kHz-10kHz =     ±(0.5% rdg + 0.5% range)
10kHz-100kHz = ±(0.7% range + 0.1%/kHz rdg), typical
 
Power AC, 50-400Hz; Fuse: Power 85V-240V; 2AF/30VA
Dielectric Strength Inputs to case or power supply
Line input to case
Input to Input
2.5kV/50Hz/1 minute
1.5kV/50Hz/1 minute
4kV/50Hz/1 minute
Dimension H x W x D; Weight 150 x 235 x 320mm; 4kg
Options IEEE-488-2, External synchronization
4 Analog inputs, low range, input impedance 200kΩ
4 Analog inputs, high range, input impedance 200kΩ
Rack mounting kit
Humidity: KYG according to DIN 40040, max. 85% RH non-condensing

0 - ±5V
0 - ±10V
Shunt Input
HiLo Ranges in mV: 60, 60(10)½, 600, 600(10)½, 6000, 6000(10)½
Accuracy : same as 5A-input
Input impedance: 200kΩ; input of 60mV corresponds to 1.0000A display.

Please email sales@hotektech.com or call 253-927-6186 if you are interested in a purchase, or
  need additional information.

[Home] [Top] [Distribution] [Contact Us]