Inputs
Universal inputs models for thermocouple (J, K, T, E, R or S under
ITS-90), 0-55mV, RTD under DIN 43760, 4-20mA, 1-5Vdc and 0-10Vdc
selected by user. Input impedance of 250 ohms for mA, 10 M ohms for
5Vdc and 2 M ohms above 5Vdc. Frequency inputs models for signals up
to 30kHz, from 300mVpp to 30Vpp and 70Vdc max. DIN 19234 compliance
for intrinsically safe NAMUR sensors.
Note: Universal or frequency inputs require different instruments.
See order code.
Control Function
On-Off Control
PID Control
PID Control with Auto-Tune
Heating-Cooling Control
Cascade Control
Programmable set-point up to 10 segments
Remote set-point
Control Outputs
4-20mA (750 ohms maximum load), 1-5Vdc or 0-10Vdc analogic output.
Up to two optional modules galvanically isolated to 300Vac from
power supply and inputs.
SPST relays rated for 3A at 220Vac.
Logic signal, open collector transistor, 40mA/24Vdc maximum with
isolation.
Alarm Outputs
SPST and SPDT relays rated for 3A at 220Vac.
Logic signal, open collector transistor, 40mA/24Vdc maximum with
isolation.
Serial
Communication
RS-232 or RS-422/485 with 50Vdc isolation.
Indication
DCY-2050: Two 9mm red LED's displays with four digits.
DCY-2051: 14mm and 9mm displays with four digits.
DCY-2060: Two 14mm red LED's displays with four digits.
Displays can be configured together with the decimal point.
Configuration
By front panel push-buttons, serial communication and internal
jumpers.
Sampling Rate
140 ms standard. Half second display update rate.
Accuracy
± 0.1% of full scale for TC, RTD, mA, mV and Vdc input.
± 0.5% of full scale for analogic output.
± the display resolution for frequency input.
Linearization
± 0.1% of full scale for RTD and ± 0.2% of full scale for TC.
Square Root
Extration
± 0.5% of reading, for input above 10% of span. Cut-Off
programmable from 0 to 5%.
Digital Filters
First order digital filters applied to the inputs with time constant
from 0.0 to 25.0 seconds.
Cold Junction
Compensation
± 2.0°C at range from 0 to 50°C ambient temperature.
2-Wire Transmitter
Power Supply
24Vdc/50mA maximum, isolated from output with short circuit
protection.
Span Temperature
Coefficient
± 0.005% of input span for °C, at 25°C ambient temperature.
Power Supply
90 to 240Vac 50/60Hz, 24Vdc, 12Vdc or other values. 10W nominal. See
order code.
Operating Ambient
0 to 50°C temperature and 90% maximum
relative humidity.
Dimensions
DCY-2050: 1/8 DIN (96x48x170mm) HxWxD, (92x45mm) HxW panel cutout.
DCY-2051: 1/8 DIN (48x96x170mm) HxWxD, (45x92mm) HxW panel cutout.
DCY-2060: 1/4 DIN (96x96x170mm) HxWxD, (92x92mm) HxW panel cutout.
Weight
0.5kg nominal.
Warranty
One-year warranty.