Inputs
Universal input model for thermocouple (J, K, T, E, R or S under
ITS-90), 0-55mV, RTD under DIN 43760, 4-20mA, 1-5Vdc and 0-10Vdc
selected by user. Auxiliary input for 4-20mA, 1-5Vdc and 0-10Vdc used
as remote set-point. Input impedance of 250 ohms for mA, 10 M ohms
for 5Vdc and 2 M ohms above 5Vdc.
Frequency input model for signals up to 30kHz, from 300mVpp to 30Vpp
and 70Vdc max. DIN 19234 compliance for intrinsically safe NAMUR
sensors.
Note: Universal or frequency input require different instruments.
See order code.
Control
Function
On-Off Control
PID Control
PID Control with Auto-Tune
Heating-Cooling Control
Cascade Control
Programmable set-point up to 10 segments
Remote set-point
Control
Outputs
4-20mA (750 ohms maximum load), 1-5Vdc or 0-10Vdc analogic output.
Up to two optional modules galvanically isolated to 300Vac from
power supply and inputs.
SPST relays rated for 3A at 220Vac.
Logic signal, open collector transistor, 40mA/24Vdc maximum with
isolation.
Alarm
Outputs
SPDT relays rated for 3A at 220Vac.
Logic signal, open collector transistor, 40mA/24Vdc maximum with
isolation.
Serial
Communication
RS-232 or RS-422/485 with 50Vdc isolation.
Indication
DCY-2050-Light: Two 9mm red LED's displays with four digits.
DCY-2051-Light: 14mm and 9mm displays with four digits.
DCY-2060-Light: Two 14mm red LED's displays with four digits.
Displays can be configured together with the decimal point.
Configuration
By front panel push-buttons, serial communication and internal
jumpers.
Sampling
Rate
140 ms standard. Half second display update rate.
Accuracy
± 0.1% of full scale for TC, RTD, mA, mV and Vdc input.
± 0.5% of full scale for analogic output.
± the display resolution for frequency input.
Linearization
± 0.1% of full scale for RTD and ± 0.2% of full scale for TC.
Square
Root Extration
± 0.5% of reading, for input above 10% of span. Cut-Off
programmable from 0 to 5%.
Digital
Filters
First order digital filters applied to the inputs with time constant
from 0.0 to 25.0 seconds.
Cold
Junction Compensation
± 2.0°C at range from 0 to 50°C ambient temperature.
2-Wire
Transmitter Power Supply
24Vdc/50mA maximum, isolated from
output with short circuit protection.
Span
Temperature Coefficient
± 0.005% of input span for °C,
at 25°C ambient temperature.
Power
Supply
90 to 240Vac 50/60Hz, 24Vdc,
12Vdc or other values. 10W nominal. See order code.
Operating
Ambient
0 to 50°C temperature and 90%
maximum relative humidity
Dimensions
DCY-2050-Light: 1/8 DIN
(96x48x170mm) HxWxD, (92x45mm) HxW panel cutout.
DCY-2051-Light: 1/8 DIN (48x96x170mm) HxWxD, (45x92mm) HxW panel
cutout.
DCY-2060-Light: 1/4 DIN (96x96x170mm) HxWxD, (92x92mm) HxW panel
cutout.
Weight
0.5kg nominal.
Warranty
One-year warranty.