Inputs
DMY-2030: Universal input model for thermocouple (J, K, T,
E, R or S under ITS-90), 0-55mV, RTD under DIN 43760,
4-20mA, 1-5Vdc and 0-10Vdc selected by user.
DMY-2030-TOT:
Universal input model for 0-55mV, 4-20mA, 1-5Vdc and 0-10Vdc
selected by user. Input impedance of 250 ohms for mA, 10 M
ohms for 5Vdc and 2 M ohms above 5Vdc.
Frequency input model
for signals up to 30kHz, from 300mVpp to 30Vpp and 70Vdc
max. DIN 19234 compliance for intrinsically safe NAMUR
sensors.
Note: Universal or frequency inputs require different
instruments. See order code.
Outputs
4-20mA (750 ohms maximum load), 1-5Vdc or 0-10Vdc analog
retransmitter.
Up to two optional modules galvanically
isolated to 300Vac from power supply and inputs.
Up to four SPST and SPDT relays rated for 3A at 220Vac.
Logic signal, open collector transistor, 40mA/24Vdc maximum
with isolation.
Note: There are 4 fitting connectors internally, so, the
total number of optional output modules is 4.
See order
code.
Serial
Communication
RS-232 or RS-422/485 with 50Vdc isolation.
Indication
DMY-2030: 14mm red LED's display with four and a half digits
which can be configured together with the decimal point.
DMY-2030-TOT: 9mm red LED's display with eight digits which
can be configured together with the decimal point.
Totalization
Range
0 to 99999999 which can be configured together with the
decimal point.
Configuration
By front-panel push-buttons and internal jumpers.
Sampling
Rate
120 ms standard. One second display update rate.
Accuracy
± 0.1% of full scale for TC, RTD, mA, mV and Vdc input.
± 0.5% of full scale for analog retransmitter output.
± the display resolution for frequency input.
Linearization
± 0.1% of full scale for RTD and ± 0.2% of full scale for
TC.
Square
Root Extration
± 0.5% of reading, for input above 10% of span. Cut-Off
programmable from 0 to 5%.
Digital
Filters
First order digital filters applied to the inputs with time
constant from 0.0 to 25.0 seconds.
Cold
Junction Compensation
± 2.0°C at range from 0 to 50°C ambient temperature.
2-Wire
Transmitter Power Supply
24Vdc/50mA maximum, isolated from output with short circuit
protection.
Span
Temperature Coefficient
± 0.005% of span for °C, at 25°C ambient temperature.
Power
Supply
90 to 240Vac 50/60Hz, 24Vdc, 12Vdc or other values. 10W
nominal. See order code.
Operating
Ambient
0 to 50°C temperature and 90% maximum relative humidity.
Dimensions
1/8 DIN (48x96x170mm) HxWxD, (45x92mm) HxW panel cutout.
Weight
0.5kg nominal.
Warranty
One-year warranty.