FLUE GAS ANALYZER TEMP EFFICIENCY
O2 CO2 |
|
| 325XL
Flue Gas Analyzer Temperature Efficiency O2, CO2 |
|
325XL
Flue Gas Analyzer Temperature Efficiency O2, CO2
Flue gas analyzer incl. rechargeable battery and calibration
protocol
The TÜV approved testo 325 XL is used by heating technicians and
fitters for measurements.
It fulfills all the requirements for
tuning, maintaining and servicing burners. TÜV for O2, CO2, °C and
CO
|
 |
-
CO measurement range up to 4000 ppm
-
Specific factors for 6 fuels selectable
-
Memory for 20 data blocks (testo 325 XL)
-
TÜV approval for CO (H2 compensated)
-
Battery recharging in analyzer
|
|
|
|
|
|
|
|
Storage temperature |
-20... +50 °C |
|
Operating temperature |
-5... +45 °C |
| |
1 |
|
Battery type |
4 AA |
|
Battery life |
8 h |
|
Weight |
450 g |
| |
ABS |
|
Probe type Type K |
|
Meas. Range |
-40 to +1000 °C |
|
Resolution |
0.1 °C |
|
Probe type Pressure probe |
|
Meas. Range |
-40... +40 hPa |
|
Accuracy (absolute) |
±0.03 hPa (-2.99... +2.99 hPa) |
|
Accuracy (relative) |
±1.5% of mv (-40... -3 hPa)
±1.5% of mv (+3... +40 hPa) |
|
Resolution |
0.01 hPa (-40... +40 hPa) |
|
Probe type Pressure Probe |
|
Meas. Range |
-200... +200 hPa |
|
Accuracy (absolute) |
±0.5 hPa (-49.9... +49.9 hPa) |
|
Accuracy (relative) |
±1.5% of mv (-200... -50 hPa)
±1.5% of mv (+50... +200 hPa) |
|
Resolution |
0.1 hPa (-200... +200 hPa) |
|
Probe type Electrochemical Probe type |
|
Meas. Range |
0... +4000 ppm CO
0... +21 Vol.% O2 |
|
Accuracy |
±5% of mv (+401... +2000 ppm CO)
±10% of mv (+2001... +4000 ppm CO) |
|
Resolution |
1 ppm CO (0... +4000 ppm CO) |
|
|
|