Pressure Vacuum Switch.
250 01 850 pico vacuum sensor switch 0 to -1 bar. max. 250 mA
250 01 805 pico vacuum - pressure sensor switch -1 to 1 bar. max. 250 mA
250 01 860 pico pressure sensor switch 0 to 10 bar. max. 250 mA
Our electronic vacuum and pressure sensors are the way of the future.
Their compact and extremely lightweight construction makes them suitable for use in handling and automation systems.
Pressure Vacuum Switch
Model | Description |
---|---|
250 01 850 | pico PSVDD Vacuum switch 0 to -1 bar |
250 01 805 | pico PSVDD Vacuum pressure switch -1 to +1 bar |
250 01 060 | pico PSPDD Pressure switch sensor 0 to +10 bar |
250 01 815 | pico PSVPD Digital vacuum pressure switch -1 to +10 bar |
250 01 860 | pico PSVPD Digital pressure switch 0 to +12 bar |
The series „pico“ is designed as an e lectronic switch
with state-of-the-art technology and best priceperformance
ratio for usage in all kind of handling
and many other industrial automation systems.
Pressure Switch specification
Electrical data, characteristics | |
Supply voltage | 11 – 30 V (inverse-polarity protection) |
Current input | < 30 mA |
Outputs | 2 x PNP-Transistor NO / NC programmable with
max. 250 mA switching current each, overload protection |
On-/Off-Delay time | 0...180 sec. programmable |
Linearity error | ≤ 1% |
Repeatability | ± 0,2 % FS |
Response time | type <2.5 ms |
Hysteresis | adjustable 0-100% of selected operating point |
Repeat accuracy | ± 0.2% of the effective range |
Error code | indicated with display |
Insulation Resistance | >100 MΩ at 500 VDC |
Voltage Withstandability | 1000 VDC 1 min |
Mechanical data, characteristics | |
Housing | ABS-PC plastic |
Connections | nickel-plated brass |
Weight | approx. 25 g |
Electrical connection | M 8x1 / 4 pin |
Pressure port | 1/8“ with M5 inside (optional NPT 1/8“) |
Operating environment conditions | |
Position | any |
Temperatures operation: | Operation: -10°... +60°C
Storage: -20° - +85°C |
max. Overpressure | max. 5 bar / max. 16 bar (10bar-Version)** |
EMC | according to EU-directive 2004/108/EG *** |
Remarks | * port downwards when using oiled air
** overpressure not continously allowed *** shielded cable recommended |
Accessories: cable connectors, adaptor flange, fixing bracket |
|
Cable connector type | Order no. |
axial length 5 m PUR M8x1x0.25 mm | 110 26 310 |
radial length 5 m PUR M8x1x0.25 mm | 110 26 300 |